IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
120
G:
lnput group number (F610/F632/F650 only)
A
: Detector average (F610/F632/F650 Analog Addressable Detectors only)
if D=6,14 ie Thermal detector then A=average temp
if D=3,5,11,13 ie Photo,lon then A=average count
S:
Detector variables (F610/F632/F650 Analog Addressable detectors only)
if D=6, 14 ie Thermal detector then S=alarm temp in °C ((S X 2) -10%)+32 = Alarm
Temp in °F)
if D=3,5,11,13 ie Photo,lon then S=sensitivity (0= High , 3 = Low Sensitivity)
C:
lnput device variable
if D=0 ie conventional zone
C
=0 no end of line resistor
C
=1 end of line resistor exists
if D=6, 14 ie Thermal detector then if
C
=1 Rate of Rise ON
C
=0 Rate of Rise OFF
If D=3, 5, 11, 13 ie Photo lon then if
C
=1
Auto compensation
is ON
C
=0 Auto compensation is OFF
Z:
Zone type
Supervisory zone
0=Supervisory zone
1 =Generic zone
Security zones
2=Passive Entry/Exit Security zone
3-Active Entry/Exit Security zone
4=Normal Security zone
5=Active Security zone
Switch zones
6=Activate/Deactivate Security zone
7=Acknowledge zone
8=Drill zone
9=Reset zone
10=Signal Silence zone
11=Abort zone
12=Dump zone