IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
69
Field Descriptions for Signal Circuits and Analog Addressable
“Ckt:xxx”
Indicates the signal circuits memory address
“Add:xxx
Address of analog relay module
“D_Type:Sig”
Shows the type of output circuit
“ALR:x”
Indicates to what alarm level the circuit will be activated in the
event that “and” zones are programmed.
>>NOTE: The use of Cross and Counting Zones must comply with the
applicable requirements of NFPA 72, 3-8.2.5:
Systems that require the operation of two automatic detection
devices to initialize the alarm response shall be permitted,
provided:
(a) They are not prohibited by the authority having jurisdiction.
(b) There are at least two automatic detection devices in each protected space.
(c) Automatic detection device area spacing is no more than one-
half that determined by the application of NFPA 72 Chapter 5.
“Sig:xxx”
Indicates the type of signaling to be output by the circuit (i.e.
steady, marchtime, etc). Refer to
Output Signal Circuit Type
for a complete
description .
“Res:xxx”
Indicates when the signal circuit has been programmed to return to
normal.
Refer to Signal Circuit Restore
for a complete
list of options.
“DRL:x”
Indicates if a signal circuit will activate when the drill switch is depressed.
“Sil:x” Auto Silence – Programmable, 2 – 15 min..
“O_Grp:xxx”
Identifies the output group.
“Seq:”
Sequentially
Restores.
>>
NOTE: If an analog addressable line (or single device) is not
programmed when selected, the result is no action.
4. Program the signal circuit by using the left/right arrow keys to move between fields and the
up/down keys to assign the desired characteristics.
5. To exit output circuit programming press the “
Enter
” key.