IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
91
Change Menu 2
Change Menu
1=Menu 1 2=Menu 2 3=Menu 3
4=Menu 4 0=Exit
>2
Change Menu 2
1=City 2=Ann 3=Trbl 4=BCKey
5=Day Enable 6=Day/Night 0=Exit
Change City
The City Tie Circuit is designed to operate in four modes of operation; Line Reversal,
Master Box, Dialer, and Chicago mode. In the Line Reversal and Dailer modes all alarms
and troubles are transmitted over the city tie circuit. In the Chicago mode the City Tie
transmits all troubles and alarms with the exception of City Tie troubles. If the City Tie
circuit detects a trouble condition the Spare relay will transfer for use with a local indicator
which indicates that troubles and alarms can’t be transmitted. In the Dailer mode AC loss
troubles are delayed for 6 hours to prevent unnecessary telephone messages.
Change Menu
1=Menu 1 2=Menu 2 3=Menu 3
4=Menu 4 0=Exit
>2
Change Menu 2
1=City 2=Ann 3=Trbl 4=BCKey
5=Day Enable 6=Day/Night 0=Exit
>1
City Tie Is In XXXXXXX Mode
Press Enter Key To Exit
Press Any Other Key To Select New Mode
Change Ann
The Change Ann option allows the user to enable and disable the supervision of the
supervised devices connected to the RS-232 port.
Change Menu 2
1=City 2=Ann 3=Trbl 4=BCKey
5=Day Enable 6=Day/Night 0=Exit
>2
Press Enter Key To Exit
Press Any Other Key To Toggle
Remote Annunciator is Detached
Remote Annunciator is Attached