IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
14
Status :Normal
MM/DD/YY HH:MM
System Idle
Figure O-1
Alarm Condition
(default)
The IF 610 will go into an ALARM
state when any analog/addressable initiation
device reports an alarm condition. By default the following actions will occur at the
common control display. Refer to Table
O-1, System Events Messages
in the
Appendix for complete listing of message displays.
1.
The red "Alarm Display" LED will begin flashing. The flash rate is a
continuously repeating sequence of 1/4 second 'On' followed by 1/4 second
'Off'. The internal system buzzer will sound.
2.
The alphanumeric display will show the identification of the
Alarm
along with
date and time. (Refer to Figure O-2) Alarm information is logged into the
History Buffer to provide a time stamped record of the event's occurrence. In
the event of multiple alarms, the alphanumeric display can be scrolled (using
the up/down arrow keys) to show all active initiating devices.
3.
The Form C common alarm relay contacts will transfer.
4.
The acknowledge switch red LED will begin to flash. This guided prompt
feature notifies the user that the next expected action is to press the "ACK"
switch - acknowledging the
Alarm Condition
.
Status : ALARM 1st of 1 MM/DD/YY HH:MM
Fire Alarm in Ckt#_ Dev#:_
Figure O-2