IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
33
Addressable Input
Devices
PID-95
Installation
Gamewell.'s IF 610 series of Addressable Input Devices provide the interface
between the IF 610 Analog circuits and contact devices. The input devices are
available as a point identification device (PID-95) and as an addressable manual
station (MS-95). Point Identification devices provide for a style B circuit.
The PID-95 is intended to provide the interface between contact devices and the
analog circuit of the IF 610. They provide a means of connecting and identifying
monitor points without the use of conventional zone modules at the main control
panel. The use of PID-95’s can drastically reduce the field wiring required on many
projects by reducing the number of wires required on the installation.
The PID-95 is designed to mount in standard electrical backboxes. When
monitoring other contact devices the unit can be mounted in a standard double gang
back box.
PID-95P is a PID-95 mounted on a 4 11/16 plastic plate where visual identification
of the device’s location is required.
MS-95
The MS-95 is an Addressable Manual Station with in and out leads. The MS-95 is
designed to mount in standard electrical backboxes.
CZI-95
The CZI-95 is a collective zone interface for the analog addressable circuit. It is
designed to power up to 25 conventional smoke detectors. It accommodates both
style B or D wiring. The CZI-95 mounts to any standard 4 11/16“ backbox and is
provided with screw terminals for wiring.
Addressable Input Devices
Installation Notes:
Electrical Specifications
PID-95, PID-95P, MS-95
CZI-95
Input Power
21 VDC
21 VDC
Quiescent Current:
.0004 amperes
10 mA
Alarm Current:
.0014 amperes
100 mA
Operating temperature
0·C to +49·C
0 to 49
°
C
Relative Humidity
85%, non-condensing
85% non-condensing
See the Compatible Device Tables in Section 6, Appendix, for other device currents.