IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
94
Change Prefix
This option allows the user to change the Prefix for alarm events that occur. The default
setting is FIRE Alarm. If the panel were monitoring Gas detectors, for example. The Prefix
could be changed to GAS and therefore display GAS Alarm during alarm conditions.
Change Menu 3
1=Abort 2=Prefix 3=Config 4=Tally
5=Sil Inh 6=AutoSil 0=Exit
>2
Current Alarm Prefix is: Fire
Enter New Alarm Prefix: XXXX
Do you want to clear prefix Y/N? N
Alarm Prefix is set to! Fire
Press any key to continue
Change
Configuration
Name
The Change Config. name option allows a textual designation of the configuration file for
archive identification..
Change Menu 3
1=Abort 2=Prefix 3=Config 4=Tally
5=Sil Inh 6=AutoSil 0=Exit
>3
Current Config String Is:
SmartStart Config
Enter New Config String:
New Name
>Enter
Do You Want To Clear String (Y/N)
>N
Change Tally
Count
The Change Tally Count option allows the selection of the number of times a Verification
detector can activate without a full alarm, in a 30 day period. If the number is exceeded the
detector is put into “Verification Trouble” status..
Change Menu 3
1=Abort 2=Prefix 3=Config 4=Tally
5=Sil Inh 6=AutoSil 0=Exit
>4
Verification Count Is Set To: 2
Enter Verification Count (2-15)