IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
119
if I=9 {Analog Addressable interface) then:
I:0
I:
lnput devices on channel number
0=1st, 1=2nd, 2=3rd, 3=4th channel
O:0
O:
Output devices on channel number
0=1 st, 1 =2nd, 2=3rd, 3=4th channel
if 1=240 or 241 (Flex500 interface) then:
I:0
I:
lnput devices on channel number
0=1st, 1=2nd, 2=3rd, 3=4th, 4=5th, 5=6th, 6=7th, 7=8th channel
O:0
O:
0utput devices on channel number
0=1st, 1=2nd, 2=3rd, 3=4th, 4=5th, 5=6th, 6=7th, 7=8th channel
Miscellaneous Card IDs
7=CCP7: Card 7, Vacant
255=Empty card slot
Input Device Variables
N:115 D:11 G:26 A:26 S:0 C:1 Z:15 B:0 1:0 2:0 3:0 4:0 5:00 Y:0
N:
Device address/number
D:
Device type (F610/F632/F650 only)
0=Conventional Circuit
2=GW-Switch Monitor (PID-95)
3=Analog Addressable-lonization 1
5=Analog Addressable-optical 1
6=Analog Addressable-Thermal 1
7=GW-MCP or Pull Box or PID
10=GW-CZI detector without interrupt
11 =Apolio-lonization 2
13=Analog Addressable-optical 2
14=Analog Addressable-Thermal 2
15=GW-CZI detector with interrupt
16=F500 Input Device
17=F500 Output Device
18=F500 Manual Device
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com