IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
104
Test Analog
The analog test is designed to allow the user to control and obtain “real time” information
about individual analog addressable devices. When analog is selected from the Test Menu
,the system prompts the user to enter the channel of the card and device address. The “Data
to Send” (0-7) prompt is expecting an entry from 0-7. This entry controls the analog device
mode of operation. There are 3 bits of information that control the state of each analog
device (see table below). The accumulated total of these bits for the desired state is the
number that should be entered at the “Data to Send” prompt. When this information is
entered, the system displays the “real time ”information including CCT#, Address #,
Device type and Counts for the device selected.
Test Menu
1=Input 2=Output 3=ID 4=Gnd
5=Lamp 6=Analog 0=Exit
>6
Enter Card # 17
Enter Channel to Poll (1-4):
Enter Address to Poll (0-127):
Enter Data to Send (0-7):
Ch:01 Add:26 D_Type:Mon. Counts:17
Flags:x08 Bits:x08
BIT4
BIT 2
BIT 1
XP95-P
Local LED
Test Mode
Remote LED
XP95-I
Local LED
Test Mode
Remote LED
XP95-T
Local LED
Test Mode
Remote LED
MS-95
Local LED
N/A
N/A
PID-95
Local LED
N/A
N/A
CZI-95
Local LED
Class “A” Relay
Zone Power Off
RCE-95
Local LED
N/A
Relay
SCE-95
Local LED
N/A
Signal Power
Figure 1: Output Control Bits
Display Panel
Description
Trouble / No
Feedback
Background Dirty
Pre-Alarm
on 1st
Alarm / Shorted
Ion Ionization
Detector
0 - 9
10 - 40
41 - 44
Background
+
26
Background
+
36
Opt. Photo
Detector
(non-comp.)
0 - 9
10 - 40
41 - 44
25 +
(sensitivity * 6)
+ 8
25 +
(sensitivity * 6)
+ 18
Opt.
Photo Detector
(Compensated
)
0 - 9
10 - 40
41 - 44
Back
(sensitivity * 6)
+ 8
Back
(sensitivity * 6)
+ 18
Heat Thermal
Detector
0 - 7
10 - Fixed
Value
NA NA
Above Fixed
Value