IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
61
The four access level default settings are:
Access level 1 = Ack.
Access level 2 = Ack., Sig. Sil., Reset, Drill
Access level 3 = Ack., Sig. Sil., Reset, Drill, Det. test, Walk Test, Bypass
Access level 4 = Programming, SmartStart
Default passwords for the access levels are:
Password 1111 = Access level 1
Password 2222 = Access level 2
Password 3333 = Access level 3
Password 4444 = Access level 4
∆∆∆∆
WARNING !
>>
When the system is in access level 4, programming, the system
will not recognize an alarm or trouble condition. The premises
should be protected by a fire watch or other reliable measure(s)
whenever the system is being programmed.
Password Entry
1. Press "Password" keypad switch. Figure 5 is now displayed.
Password Entry Screen
Enter Password:
Security Level: X
User ID: XXX
Figure 5
2. To change access levels, enter the appropriate password on the keypad.
3. To enter the programming mode after a system configuration, enter the password access LEVEL
4.
>>
NOTE: System will exit the Programming mode and commence a Reset after 5 minutes of
inactivity.