A:0 R:1 D:2 S:1 B:2 W:2 F:2 C:0 T:2 Y:2
A:
Acknowledge Security level
R:
Reset Security level
S:
Signal Silence Security level
D:
Drill Security level
B:
Bypass Security level
W:
Walk Test Security level
F:
Function Key Security Level (F610/F632/F650 systems only)
C:
City Connection type (0=Line Reversal, 1=Local Energy Master Box
2=Chicago 3=Dialer)
T:
Detector Test Security level (F610/F632/F650 systems only)
Y:
Day/Night Security level
A:0 B:0 E:0 D:0 H:17 M:0 V:2 W:30 R:30 P:30
A
= Abort key types
0 =
One Shot
. Abort stops timer while held, release after time out. Switch can be
activated only once (default)
1 =
Time Expirey
. Abort prevents release while held, release after timer expires and
Abort switch released. Multiple actuations allowed
2 =
Immediate
. Abort disables programmed timer, release immediately after switch
deactivation
3 =
10 Sec Delay
. Abort disables programmed timer, release 10 to 18 sec after
switch deactivation
4 =
Reset Timer
. (Not UL) Abort resets programmed timer while held, release when
timer expires. Multiple actuations allowed
B
= BC key Supervision control
0=BC keys are not supervised (default)
1=BC keys are supervised
E
= Day/Night key enable control
0=Day/Night key not enabled (default @ SmartStart)
1=Day/Night key enabled
D
= Day/Night operation control
0=Day/Night operation is Manual (default @ SmartStart)
1=Day/Night operation is Automatic
H
= Day mode exit time hour
Valid entries 0-23 (17 default @ SmartStart)
M
= Day mode exit time minutes
Valid entries 0-59 (0 default @ SmartStart)