Addendum for IF 600 Firmware Ver. 7.1
Issue A 9/27/01
4
Multisensor Detector (Cont.)
DEVICE TEST TABLE
Input Device
Display
Panel
Description
Trouble /
No
Feedback
Background
Dirty
Pre-Alarm
on 1st
Alarm / Shorted/
Active
Ion Ionization
Detector
0 - 9
10 - 40
41 - 44
Background
+
26
Background
+
36
Opt. Photo
Detector
(non-comp.)
0 - 9
20 - 30
41 - 44
25 +
(sensitivity x 6) + 8
25 +
(sensitivity x 6)
+ 18
Opt.
Photo Detector
(Compensated)
0 - 9
10 - 40
41 - 44
Back
(sensitivity x 6) + 8
Back
(sensitivity x 6)
+ 18
Heat Thermal
Detector
0 - 7
10 - Fixed
Value (ºC)
NA NA
Above Fixed Value
Multi Multisensor
Detector
0 - 9
18 - 32
33 - 44
45 - 54
55 - 127
CZI or
CZII
CZI-95
0 - 16
17 - 54
NA NA
55 - 122
2nd Alarm above
122
PID or
MAN
PID - 95 or
MS - 95
0 - 9
10 - 54
N/A
N/A
55 - 127
REL
RCE - 95
0 - 14
15 - 45
NA NA
46 - 127
RSM
RSM-95
0 – 14
15 – 45
NA NA
46 - 127
SCE or
Snd.
SCE - 95
0 - 14
15 - 45
NA NA
46 - 127
DEVICE TYPE TABLE - P3
Display Panel
Description
Ion. Ionization
Sensor
Opt .
Photo-Electric Sensor
Heat Thermal
Sensor
Multi
Multi sensor, combined Photo and Thermal sensing
Mon.
Point Identification Device (contact monitor)
Man.
Manual Station (or PID with priority interrupt set)
CZI
Collective Zone Interface
CZII
Collective Zone Interface (with priority interrupt set)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com