background image

4 & 8 Zone Fire Alarm Panels

System installation, operating & maintenance
instructions

These instructions cover the:

ÿ

SECURI4:

Four-Zone Conventional Fire Panel

ÿ

SECURI8:

Eight-Zone Conventional Fire Panel

The panels are designed to meet the requirements of EN54-2:1996 &

EN54-4:1996

Technical helpline:

+44 (0) 1268 56 3256

This publication is issued to provide outline information only and is not deemed to

form part of any offer or contract

.

Our policy is one of continual improvement and

we reserve the right to vary details without prior notice.

General Description

Options included that are covered by EN54

ÿ

Test Condition (10.0)

ÿ

Fire Alarm Devices (7.8)

Ancillary functions provided but not required by EN54

ÿ

Class change & Repeater

Technical Specifications

Power Supply requirements

10 - 15% 50Hz
Maximum Power consumption 45VA
Fuse rating - T250mA

Battery

24 Hour standby

1 x 12 V 7.0 Ah Yuasa

Fuse rating - F6.3A

Weight

6 Kg (including 7.0 Ah battery) approx.

Detection Circuits

20 smoke or heat detectors maximum per zone, (A maximum quiescent

current of 1.2mA is allowed per zone circuit)
30 Call Points maximum per zone.

Alarm Sounder Circuits

0.8A total through 2 circuits.
Nominal Voltage 25V (+/-1V)
Fuse rating - F1A

Auxiliary 24V Supply

This is specifically not for fire protection devices.

50mA maximum.

Nominal Voltage 25V (+/-1V)
Fuse rating - F100mA

Auxiliary Fault Output

Normally 24V max. 30mA
Fault indication -ve output floats

Auxiliary Fire Relay

Two sets of auxiliary contacts (DPCO) rated at 30VDC 1A. This facility is

not to be used for fire alarm routing equipment.

Class Change

Activated by using volt free N/O contacts between the -ve of AUX 24V

output and the CLASS CHANGE output.

Cabling

Unless otherwise recommended, and taking into account voltage drop, not

less than 1mm

2

is recommended.

Sounder circuits should use cable that is fire proof.
All cabling should be earthed to the metal back box via the cable gland.
Conductors carrying fire alarm power signals should be separated from

conductors used for carrying other systems.

Installation Information

Installation of this product must be carried out using the information given

in this leaflet by a qualified electrician.

Warning:

Before installation ensure the electrical supply is

isolated.

Installation of this product must be carried out in accordance with the

requirements of BS5839 Pt1 and EN54.

Mounting location considerations

The fire alarm control panel should be mounted near to a permanent, low

fire risk, Entry / Exit, for easy access by the Emergency Services. The

panel should not be mounted in direct sunlight, or in a place where the

ambient temperature is above 30 ºC (86 ºF).

Mains must not be capable of being accidentally disconnected and the

isolating switch should clearly state

FIRE SYSTEM - DO NOT SWITCH OFF

Caution

: Anti static precautions should be taken when

installing the panel.

61600970 issue 9_8/02

1

1

2

3

4

5

Soun

ders

ON

/OFF

Mu

te Pa

nel

Res

et

Adv

anc

e

Select

1

2

3

4

ZON

E F

AU

LT

/ TE

ST

/ DIS

AB

LE

ZON

E F

IRE

FIR

E

Pow

er

Gen

era

l Fa

ult

Sou

nde

r Fa

ult/

Dis

able

Sys

tem

Fau

lt

Pow

er F

ault

Dis

able

d

Tes

t

Sup

erv

iso

r

mo

de

LED

Con

tinu

ous

DIS

AB

LE/T

EST

LED

flas

hin

g

FAU

LT

Cod

e en

try

mo

de

Summary of Contents for SECURI4

Page 1: ...rated at 30VDC 1A This facility is not to be used for fire alarm routing equipment Class Change Activated by using volt free N O contacts between the ve of AUX 24V output and the CLASS CHANGE output Cabling Unless otherwise recommended and taking into account voltage drop not less than 1mm2 is recommended Sounder circuits should use cable that is fire proof All cabling should be earthed to the met...

Page 2: ...ransformer output to the PCB terminals marked AC Note Polarisation of this connection is unimportant 4 Connect resistors supplied between the ve and ve of each detector zone and sounder zone via the terminal blocks on the PCB carrier At this stage it is not necessary to connect detector or sounder circuits 5 Connect to repeater and volt free auxiliary terminal block as necessary 6 Re instate the m...

Page 3: ...Reinstate the mains supply enter access code then press the RESET button 8 Refit plastic facia Do not over tighten two retaining screws 61600970 issue 9_8 02 3 4 8 zone Fire alarm panels Base of existing range of detectors 1 DETECTOR ZONE FIRE PANEL L2 L1 OUT IN L1 DIODE SCHOTTKY L2 L1 OUT IN L1 DIODE SCHOTTKY Black Red or Orange Active End of Line Remote LED LED module Connecting LED to base with...

Page 4: ...d then automatically reset 1 Enter the access code to get into supervisor mode if not already entered 2 Hold down the ADVANCE push button for at least 2 seconds until you hear a double bleep 3 The Test LED will light and the Zone 1 Fault LED will flash at a fast rate faster than the fault warning flash rate the flashing LED at this stage indicates that the zone is not in test 4 If you do not wish ...

Page 5: ...g reset whilst the sounders are disabled will not revert the panel to normal operation If the panel is left in Test for more than 10 minutes the internal buzzer will sound intermittently 61600970 issue 9_8 02 5 4 8 zone Fire alarm panels Sounder General Fire General Fault Zone Fault Zone Fault Disable Test Sounder Fault Disable System Fault Power Power Fault Disabled Test Supervisor Mode Code Entr...

Page 6: ...e address___________________________________________________________________________ _______________________________________________________________________________________ Person s responsible________________________________Date_______________________________ System installed by__________________________________Telephone__________________________ Date installed____________________________________...

Page 7: ...61600970 issue 9_8 02 7 4 8 zone Fire alarm panels Fire panel event record Date Weekly Qtly Event Action Required Completed Name ...

Page 8: ...8 61600970 issue 9_8 02 4 8 zone Fire alarm panels Date Weekly Qtly Event Action Required Completed Name ...

Reviews: