Mounting Instructions

In order to minimise the installation time, it is strongly recommended, that

the following procedure is followed:

1

Remove plastic facia and detach the PCB carrier by slackening the

two carrier retaining screws.

2

Disconnect the low volt AC input wires coming from the step down

transformer to the PCB.

NOTE: DO NOT REMOVE THE PCB FROM CARRIER

.

3

Lift carrier off via the keyhole slots. Place the carrier in a safe static

free environment.

4

Using the metal back box as a template, prepare the four fixing holes

and mount to wall using appropriate mounting system.

5

Prepare cable entries via the 20mm knockouts provided in the top

and rear of back box using appropriate glanding system. DO NOT

USE TOP LEFT GLAND POSITION.

6

Feed in all required cabling and prepare ends ensuring there is

sufficient lead length to enable connection to terminal blocks in back

box and on PCB carrier. Refer also to Technical Specification –

Cabling.

7

Remove all debris from back box.

Initial wiring and power up tests

1

Connect AC supply to terminal block in back box as marked.

NOTE:

AN EARTH CONNECTION MUST BE MADE TO

THE TERMINAL BLOCK AS MARKED.

2

Replace the PCB carrier via the key hole slots and tighten

retaining screws.

3

Reconnect the transformer output to the PCB terminals

marked ‘AC~’.

Note: Polarisation of this connection is unimportant

4

Connect resistors (supplied) between the +ve and -ve of each

detector zone and sounder zone via the terminal blocks on

the PCB carrier.

At this stage it is not necessary to connect

detector or sounder circuits

.

5

Connect to repeater and volt free auxiliary terminal block as

necessary.

6

Re-instate the mains supply.

The panel is now active and will

indicate a ‘System Fault’, ‘Power Fault’ (No Battery) and

‘General Fault’ until reset.

7

Fit battery into bottom of back box and connect battery the

leads supplied. Ensure correct polarity is always observed.

8

Check panel is operating normally. Enter the 4-digit security

code as noted on inside of the panel cover and press ‘Reset’.

The ‘System Fault’, ‘Power Fault’ and ‘General Fault’ will

clear and the ‘Power’ lamp will remain illuminated. For further

information about ‘Reset’ procedure see operating

instructions.

2

61600970 issue 9_8/02

4 & 8  zone - Fire alarm panels

Fuses

Transformer

terminals

low volt

AC input

Battery

terminal

8K2 Ohms

End of line

Resistor

SOUNDER AND DETECTOR

TERMINAL BLOCKS

ACTIVE

END OF LINE

DEVICE

RED

OR ORANGE

BLACK

DETECTOR

SOUNDER

1A

1

2

AUX 24V

250mA

6.3A

RED

BLACK

Figure 2 Terminals and fuses

Carrier

retaining

screws

Housing

Cable entry

points (top and back)

Carrier &

PCB assembly

PCB Terminal

blocks

Battery

Mains supply terminal bock

Transformer

Figure 1 Panel with cover removed

Summary of Contents for SECURI4

Page 1: ...rated at 30VDC 1A This facility is not to be used for fire alarm routing equipment Class Change Activated by using volt free N O contacts between the ve of AUX 24V output and the CLASS CHANGE output Cabling Unless otherwise recommended and taking into account voltage drop not less than 1mm2 is recommended Sounder circuits should use cable that is fire proof All cabling should be earthed to the met...

Page 2: ...ransformer output to the PCB terminals marked AC Note Polarisation of this connection is unimportant 4 Connect resistors supplied between the ve and ve of each detector zone and sounder zone via the terminal blocks on the PCB carrier At this stage it is not necessary to connect detector or sounder circuits 5 Connect to repeater and volt free auxiliary terminal block as necessary 6 Re instate the m...

Page 3: ...Reinstate the mains supply enter access code then press the RESET button 8 Refit plastic facia Do not over tighten two retaining screws 61600970 issue 9_8 02 3 4 8 zone Fire alarm panels Base of existing range of detectors 1 DETECTOR ZONE FIRE PANEL L2 L1 OUT IN L1 DIODE SCHOTTKY L2 L1 OUT IN L1 DIODE SCHOTTKY Black Red or Orange Active End of Line Remote LED LED module Connecting LED to base with...

Page 4: ...d then automatically reset 1 Enter the access code to get into supervisor mode if not already entered 2 Hold down the ADVANCE push button for at least 2 seconds until you hear a double bleep 3 The Test LED will light and the Zone 1 Fault LED will flash at a fast rate faster than the fault warning flash rate the flashing LED at this stage indicates that the zone is not in test 4 If you do not wish ...

Page 5: ...g reset whilst the sounders are disabled will not revert the panel to normal operation If the panel is left in Test for more than 10 minutes the internal buzzer will sound intermittently 61600970 issue 9_8 02 5 4 8 zone Fire alarm panels Sounder General Fire General Fault Zone Fault Zone Fault Disable Test Sounder Fault Disable System Fault Power Power Fault Disabled Test Supervisor Mode Code Entr...

Page 6: ...e address___________________________________________________________________________ _______________________________________________________________________________________ Person s responsible________________________________Date_______________________________ System installed by__________________________________Telephone__________________________ Date installed____________________________________...

Page 7: ...61600970 issue 9_8 02 7 4 8 zone Fire alarm panels Fire panel event record Date Weekly Qtly Event Action Required Completed Name ...

Page 8: ...8 61600970 issue 9_8 02 4 8 zone Fire alarm panels Date Weekly Qtly Event Action Required Completed Name ...

Reviews: