Operating instructions
Access to “SUPERVISOR MODE” for panel
operation
To operate this fire alarm control panel, it is necessary to gain access to
the “Supervisor Mode”, to do this enter the four digit security password
code, on the push buttons. This security code should have been given to
the responsible person on system hand over.
After entering the correct code the “Supervisor Mode” LED will illuminate.
The panel will time out of “Supervisor Mode” if the ‘RESET’ button is
pressed or 20 seconds have elapsed since the last button was pressed.
The following functions can all be employed in the “Supervisor
Mode”.
Sounders ON/OFF
If the panel is in alarm the sounders will sound, the sounder circuits may
be silenced by pressing this button. If the sounders are silent by pressing
this button they will be activated.
Mute panel
To silence the panel’s internal buzzer press “Mute Panel”. The panel will
continue to beep every 8 seconds until reset.
Reset
This will clear any non-latched indications and return the panel to “Code
Entry Mode”. If the cause of the indication is still present the indication will
be re-established within 10 seconds.
Select - Lamp Test
Hold down “Select” for a minimum of 2 seconds. Release
once test
complete.
Test Zone
This feature allows one person to check the detectors and sounders
without having to return to the panel during the testing routine. When the
appropriate zone is in test mode and a detector is activated, the sounder
circuit/s will operate for a few seconds and then automatically reset.
1
Enter the access code to get into “supervisor mode” if not already
entered.
2
Hold down the ‘ADVANCE’ push button for at least
2 seconds until you hear a double bleep.
3
The “Test” LED will light and the Zone 1 Fault LED will flash at a fast
rate (faster than the fault warning flash rate) the flashing LED at this
stage indicates that the zone is not in test!
4
If you do not wish to test this zone then press ‘ADVANCE’ to move
on to the next zone.
5
To put the zone into “Test” press ‘SELECT / LAMPTEST’ (repeated
pressing of this button will toggle the zone in and out of test mode!).
6
After you have pressed the select button you will see that the zone is
now constantly lit, this indicates that the zone is now in test!
7
Once the site tests have been completed you may find that the
keypad access timer has elapsed and that you will have to repeat
points 1-4 to get to the appropriate zone in test.
8
To cancel the test mode and return a zone back to normal operation
simply press ‘SELECT / LAMP TEST’ to toggle the zone from
constant to flashing.
Once you have returned the zone/zones to normal operation you can then
press reset to exit supervisor mode.
Note: Pressing reset whilst a zone is in test will not revert the panel to
normal operation!
4
61600970 issue 9_8/02
4 & 8 zone - Fire alarm panels
1
2
3
4
5
Sounders
ON/OFF
Mute Panel
Reset
Advance
Select
1
2
3
4
ZONE FAULT / TEST / DISABLE
ZONE FIRE
FIRE
Power
General Fault
Sounder Fault/
Disable
System Fault
Power Fault
Disabled
Test
Supervisor
mode
LED Continuous
DISABLE/TEST
LED flashing
FAULT
Code entry
mode
Green indicator
Red indicators
Amber indicators
Amber indicators
Control buttons
Figure 7 Controls and indicators