OPERATION - 3
3.5
STARTING THE BURNER
ALL MODELS
1. Press the control switch to PUMP AND BOILER position, the Low Water audible alarm will
sound, the Low Water Reset and Low Water alarm lights will illuminate.
2. Press the Low Water Reset switch for two seconds maximum. The alarms will stop, and the
alarm lights will extinguish.
The burner start sequence will commence.
3.
After a maximum of one minute the burner should be firing, and the Main Gas light ON.
4. When the boiler has achieved the required (set) pressure, the main steam isolating valve
should be slowly opened allowing steam to enter the system distribution pipework.
This can be achieved by one of two methods:
a) Crack open the main steam valve and allow the system to heat up slowly (minimum
15 minutes) before fully opening the main steam valve.
b) Open the main steam valve when starting the boiler, allowing the boiler and system to heat
up together.
Note: This can lead to water logging of the steam lines until full pressure is achieved.
If fitted, TDS Panel Mounted Controllers (BC3150) must be reset after any break in electrical supply to the unit.
WARNING
The system should be raised to temperature slowly to allow for expansion and to avoid thermal shock
and water hammer.
!