MAINTENANCE - 4
25. Remove the water level gauge (sight glass) and water column. Rod through the top
connections of both to ensure that the holes in the baffle plates (approx. 6 mm dia.) inside the
boiler are not obstructed.
26. Check the burner combustion to ensure that excess air and carbon monoxide values are
within normal limits (see combustion values in
Appendix A - TI-117-J Series Dimensions &
Specification
).
27.
Check the condition of the gas valve filter (if fitted), renew as required.
Cleaning
the Flues
Remove cover
plates and gasket
Remove the clean-out door
to the flue passes and to
the bottom of the boiler.
Oil boiler illustrated.
Figure. 29 - Flue Cleaning
Figure. 30 - Boiler Furnace
Figure. 31 - Ignition Electrode
Insulating rope
Refractory
brick in place