APPENDIX - B
APPENDIX B - WATER
LEVEL PROBE INFO
The Terminal & Securing Nuts are tightened to a specified torque during manufacture which
causes the PTFE Insulation to seal against the probe body. Therefore these nuts must not be
adjusted because the seal will be broken which may cause the probe to leak (see
Figure. 34
).
Angle Rajah
ONLY
must be used to connect wire to the probes because they clip directly to the
Terminal Nut. Spade Connectors must
NOT
be used because the Terminal Nut would require
adjustment and therefore cause the probe to leak (see
Figure. 35
).
N.B. The Probe Rod Grub Screw and Lock Nut are suitably tightened during manufacture,
meaning the probe is ready to be installed without any adjustment.
The
ONLY
instance a spanner should be used, is to turn the Probe Body in order to remove or
reinstall the entire probe.
IMPORTANT
Terminal and securing nuts must not be adjusted.
Only Angle Rajah are to be used to connect wire to the probes.
!
Terminal nut
Probe body
Probe rod
Securing nuts
PTFE
Insulation
Probe rod
grub screw
Probe rod
lock nut
Terminal nut
Angle rajah
Probe body
Probe wire
Figure. 34 - Water Level Probe Components
Figure. 35 -
Angle Rajah Fitted to Probe