JGASUK-IOMM-2015-2
Fulton Ltd
Page 43
MAINTENANCE - 4
Symptom and
identification symbol
Cause
Remedy
No Start
1. No Power
Check all fuses/circuit breakers
Check for correct wiring.
2. External Interlocks
Check all external interlocks are made.
3. Air Pressure Switch
Check that the switch is in ‘No Air’ position.
4. CPI switch
If fitted, must be made.
5. Air Damper
If fully closing damper fitted, check relevant micro
switch on damper.
6. Burner Motor fault
Check overload.
Lockout
1. False flame detected
Check for stray light (cell only). Faulty cell or
damaged flame probe.
Interruption of
start-up sequence
1. Air Damper
Check fully open microswitch is made.
Lockout
1. Air Pressure Switch
Check that switch is made.
P
2.
Note:
Any air pressure
failure after this time will
cause a lockout condition.
Lockout
3. Flame supervision
Check for stray light (cell only).
Faulty cell or damaged flame probe.
Interruption of
start-up
sequence
1. Air Damper
Check low fire microswitch is made.
Lockout
1. No ignition spark
Check supply ignitor.
Check electrode and HT leads for damage.
1
2. No pilot flame
Check gas supply.
Check electrode setting.
Check functionality of pilot gas valve(s).
Check pressure gas downstream of pilot valve(s).
3. Pilot lights then extinguishes
Note:
Any flame signal
failure after this stage will
cause a lockout condition
Check flame stability with ignition off.
Check air pressure at burner.
Check gas pressure is steady.
Check the flame is being sensed, i.e.
(i) Check sensor for damage.
(ii) Check sensor can view flame.
(iii) Check flame signal,
see data sht. LFL1 - 7451
4.12.3
TROUBLESHOOTING
BURNER CONTROL UNIT-LFL 1 (SIEMENS)
CONTINUED ON NEXT PAGE