Loosen the captive screws in the sequence printed on the heat sink (1 to 4)
by proceeding as follows:
Torque: 0.9 Nm
▶
First, loosen the captive screws 1 and 2 completely.
▶
Loosen the captive screws 3 and 4 completely.
▶
Push the four latches inward.
Figure 242: Removing the LC heat sink (B)
▶
Proceed for the second heat sink in the same way.
▶
Hold the heat sinks with both hands and lift up the complete LC kit.
CAUTION
▶
Pay special attention not to damage any system board
components surrounding the CPU socket.
Liquid cooling (LC)
RX2540 M6
Upgrade and Maintenance Manual
373