"Switching on the server" on page 49
.
▶
BIOS settings are automatically reloaded. Time and date must be set
manually, see
"Verifying the system time settings" on page 70
.
13.4
System board
13.4.1
Replacing the system board
Field Replaceable Unit
(FRU)
Hardware: 40 minutes
Software: 20 minutes
Tools:
Replacing the system board:
– Phillips PH2 / (+) No. 2 screw driver
– Hexagon 7 mm screw driver (for stand-offs)
– Magnifying glass for inspecting CPU socket springs
(recommended)
Preliminary steps
▶
"Locating the defective server" on page 37
.
▶
"Verifying the system time settings" on page 70
▶
"Shutting down the server" on page 37
▶
"Disconnecting the power cord (AC PSU)" on page 38
.
▶
Disconnect all external cables.
▶
"Getting access to the component" on page 39
▶
"Removing a hot-plug PSU" on page 79
.
▶
"Removing a riser module" on page 50
.
▶
Remove all air ducts, see
"Removing the air ducts" on page 62
▶
Remove the AOC card and the corresponding riser card, see
the defective riser card" on page 141
.
System board and components
194
Upgrade and Maintenance Manual
RX2450 M1