SPECIFICATIONS
1.
Type
INVERTER HEAT PUMP
Model name
AOTG18KMCA
AOTG22KMCA
AOTG24KMCA
Power source
240 V ~ 50 Hz
Available voltage range
198 V - 264 V
Starting current
A
6.0
7.5
9.0
Fan
Airflow
rate
Cooling
I/s
(m
3
/h)
569 (2,050)
622 (2,240)
739 (2,660)
Heating
500 (1,800)
681 (2,450)
681 (2,450)
Type × Q'ty
Propeller fan × 1
Motor output
W
49
Sound pressure level
Cooling
dB (A)
47
49
52
Heating
48
52
52
Sound power level
65
70
70
Heat exchanger type
Dimensions
(H × W × D)
mm
Main: 588 x 881 x 36.4
Sub: 546 x 580 x 18.2
Fin pitch
1.45
Rows × Stages
Main: 2 × 28
Sub: 1 × 26
Pipe type
Copper
Fin
Type (Material)
Corrugate (Aluminum)
Surface treatment
Corrosion resistance (Blue fin)
Compressor
Type × Q'ty
Rotary × 1
Motor output
W
1200
Refrigerant
Type
R32
Charge
g
1270
Refrigerant oil
Type
POE
Enclosure
Material
Steel
Colour
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
620 × 790 × 290
Gross
713 x 945 x 395
Weight
Net
kg
40
Gross
44
Connection pipe
Size
Liquid
mm
Ø 6.35
Gas
Ø 12.70
Method
Flare
Pre-charge length
m
20
Max. length
30
Max. height difference
20
Operation range
Cooling
°C
-10 to 46
Heating
-15 to 24
International protection rating
IPX4
NOTES :
Specifications are based on the following conditions.
•
•
Cooling: Indoor temperature of 27 °CDB / 19 °CWB and outdoor temperature of 35 °CDB / 24 °CWB.
Heating: Indoor temperature of 20 °CDB / 15 °CWB and outdoor temperature of 7 °CDB / 6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Outdoor unit - Indoor unit)
The protective function may work when using it in environment out of the temperature range mentioned above.
•
•
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...