Trouble shooting 15
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
26.9
35.2
46.6
62.3
84.2
115.2
Resistance Value (k )
Temperature
OK
OK
OK
OK
20.7
6.4
8.0
10.0
12.6
16.1
Resistance Value (k )
Temperature
Outdoor temp. sensor error
Outdoor unit Main PCB
Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-17
-15°C
-20°C
224.3
-30°C
159.7
-25°C
35°C
5.2
40°C
4.2
45°C
3.5
50°C
2.8
55°C
30°C
25°C
10°C
5°C
0°C
-5°C
-10°C
20°C
15°C
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit : Operation lamp: 7 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 74]
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
1
2
3
4
1
2
3
4
1
2
3
1
2
3
CN71
CN70
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...