4-3. Refrigerant Piping Work
Flare less joint nut assy
4-3-1 The method of tightening
CAUTION
Do not remove the tightening nut and fixing nut that are attached to the indoor unit.
(image below) (the interior O-ring has been removed)
If the fl are less joint nut assy has been loosened after it has been completely tightened,
replace with a new fl are less joint nut assy.
When removing the piping to relocate or repair the unit, replace with a new fl are less
joint nut assy.
Tightening nut
(hexagon)
Guard
Joint (Indoor unit pipe)
Indoor unit pipe
(Body side)
Mark the margin around the connection pipe
for inserting into the flare less joint nut assy.
L
Connection pipe dia. [mm (in.)]
L [mm]
6.35 (1/4) dia.
9.52 (3/8) dia.
22
23
Step-2. Peel off the seal
Peel off the seal on the tightening nut.
Connection pipe
Step-1. Mark the margin around the connection pipe
Seal
Fixing nut (circular)
(Guard covers the fixing nut)
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...