03-03
Settings will not be changed if invalid numbers or setting values are selected.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation
conditions using the remote controller.
This procedure changes to the function settings used to control the indoor unit according to
the installation conditions. Incorrect settings can cause the indoor unit malfunction.
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. ( ) simultaneously,
press the RESET button to enter the function setting mode.
3-1-2 Procedures to change the Function Setting for wireless RC
(2) Press the POWERFUL button to proceed to setting value.
(Press the POWERFUL button again to return to the function number selection.)
(3) Press the TEMP. ( / ) buttons to select the setting value.
(Press the 10°C HEAT button to switch between the left and right digits.)
Selecting the Function Number and Setting Value
(6) After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again.
The function setting does not become active unless the power is turned off then on again.
(4) Press the MODE button, and START/STOP button, in the order listed to
confirm the settings.
(1) Press the TEMP. ( / ) buttons to select the function number.
(Press the 10°C HEAT button to switch between the left and right digits.)
(5) Press the RESET button to cancel the function setting mode.
Function Number
Setting
Value
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...