En-12
16. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
flow switching, and other remote control unit operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.
17. ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error
codes by way of blinking patterns. If you use a wired remote controller, error codes will ap-
pear on the remote control display. See the lamp blinking patterns and error codes in the
table. An error display is displayed only during operation.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
●
(1)
●
(1)
◊
Serial communication error
●
(1)
●
(2)
◊
Wired remote controller
communication error
●
(1)
●
(5)
◊
Check run unfinished
●
(2)
●
(1)
◊
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
●
(2)
●
(2)
◊
Indoor unit capacity error
●
(2)
●
(3)
◊
Combination error
●
(2)
●
(4)
◊
• Connection unit number error
(indoor slave unit)
[Simultaneous Multi]
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
●
(2)
●
(7)
◊
Master unit, slave unit set-up error
[Simultaneous Multi]
●
(3)
●
(2)
◊
Indoor unit PCB model
information error
●
(3)
●
(5)
◊
Manual auto switch error
●
(4)
●
(1)
◊
Room temp. sensor error
●
(4)
●
(2)
◊
Indoor unit Heat Ex. Middle temp.
sensor error
●
(5)
●
(1)
◊
Indoor unit fan motor error
●
(5)
●
(3)
◊
Drain pump error
●
(5)
●
(7)
◊
Damper error
●
(5)
●
(8)
◊
Intake grille error
●
(5)
●
(15)
◊
Indoor unit error
●
(6)
●
(2)
◊
Outdoor unit main PCB model
information error or
communication error
●
(6)
●
(3)
◊
Inverter error
●
(6)
●
(4)
◊
Active filter error, PFC circuit error
●
(6)
●
(5)
◊
Trip terminal L error
●
(6)
●
(10)
◊
Display PCB microcomputers
communication error
●
(7)
●
(1)
◊
Discharge temp. sensor error
●
(7)
●
(2)
◊
Compressor temp. sensor error
●
(7)
●
(3)
◊
Outdoor unit Heat Ex. liquid temp.
sensor error
●
(7)
●
(4)
◊
Outdoor temp. sensor error
●
(7)
●
(5)
◊
Suction Gas temp. sensor error
●
(7)
●
(6)
◊
2-way valve temp. sensor error
•
3-way valve temp. sensor error
•
●
(7)
●
(7)
◊
Heat sink temp. sensor error
●
(8)
●
(2)
◊
Sub-cool Heat Ex. gas inlet
•
temp. sensor error
Sub-cool Heat Ex. gas outlet
•
temp. sensor error
●
(8)
●
(3)
◊
Liquid pipe temp. sensor error
●
(8)
●
(4)
◊
Current sensor error
●
(8)
●
(6)
◊
Discharge pressure sensor error
•
Suction pressure sensor error
•
High pressure switch error
•
●
(9)
●
(4)
◊
Trip detection
●
(9)
●
(5)
◊
Compressor rotor position
detection error
●
(9)
●
(7)
◊
Outdoor unit fan motor error
●
(9)
●
(9)
◊
4-way valve error
●
(10)
●
(1)
◊
Discharge temp. error
●
(10)
●
(3)
◊
Compressor temp. error
●
(10)
●
(4)
◊
High pressure error
●
(10)
●
(5)
◊
Low pressure error
●
(13)
●
(2)
◊
Branch boxes error
[Flexible Multi]
Display mode
●
: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
[Troubleshooting with the indoor unit display]
OPERATION indicator (green)
TIMER indicator (orange)
ECONOMY indicator (green)
[Troubleshooting with the Wired Remote Controller Display (Option)]
If an error occurs, the following display will be shown. (“Er” will appear in the set room
temperature display.)
Error code
ASTG18KMCA_中型標準モデルLM系_R32_0724m.indd 12
2013/07/24 16:52:26
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...