23. DEFROST OPERATION CONTROL
01-15
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects
the temperature lower than the values shown in Table19.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 20.
( Table 20 : Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +13°C.
or Compressor operation time has passed 15 minutes.
( Table 19 : Condition of starting Defrost Operation )
1 time defrosting
after starting operation
ST
Defrosting after 2 time
upon starting operation
ND
Compressor integrating operation time
Compressor integrating operation time
Compressor integrating operation time
Less than 22 min.
22 to 62 min.
More than 62 min.
Does not operate
- 9°C
- 5°C
Less than 35 min.
More than 35min.
Does not operate
Integrating defrost
(Constant monitoring)
More than 240 min.
(For long continuous operation)
Less than 10min.*1
(For intermittent operation)
- 3°C
More than 215 min.
(For long continuous operation)
- 5°C
OFF count of the compressor
40 times.
*1 : If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
Tn-Tn10 < - 5deg
Tn-Tnb < - 2deg
However, Tn < - 6°C
=
Tn10 : Temperature of continuous operation at 10minutes.
Tnb : Back 5minutes temperature
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...