Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 :
Check Indoor unit electric components
YES
YES
NO
Trouble shooting 4
INDOOR UNIT Error Method:
Indicate or Display:
Indicate or Display:
Indoor unit PCB model
information error
Indoor unit Controller PCB
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 :
Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a non-
volatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
02-06
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 3 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 32]
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...