Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Replace Main PCB
YES
YES
NO
Trouble shooting 9
OUTDOOR UNIT Error Method:
Outdoor unit main PCB model
information error
Outdoor unit Main PCB
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related
cables near the power line.
Change Main PCB.
Access to EEPROM failed due to some cause after outdoor unit started.
02-11
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 6 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 62]
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...