02-02
Trouble shooting 1-1
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 11]
YES
YES
NO
3
L
N
RED
WHITE
BLACK
+
-
OK
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V (AC220V -10%) - 264V (10%) appears
at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC90V and AC270V at Outdoor Unit Terminal L - 3.
>> If it is abnormal, Check Outdoor unit fan motor (PARTS INFORMATION 5)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If Outdoor fan motor is normal, replace Main PCB.
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 2minutes after power ON, or the indoor unit cannot receive
the serial signal more than 15seconds during normal operation.
2-2 TROUBLE SHOOTING WITH ERROR CODE
Serial communication error
(Serial Reverse Transfer Error)
Outdoor unit Main PCB
Outdoor unit fan motor
Summary of Contents for AOTG36LATT
Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Page 30: ...1204G4067 ...
Page 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Page 60: ...1205G4083 ...
Page 85: ...1307G4239 ...
Page 113: ......
Page 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 135: ......
Page 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 169: ......
Page 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Page 181: ......
Page 187: ......
Page 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Page 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Page 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Page 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Page 264: ...1208G4097 ...