![Fuji Electric ZSS-7 Instruction Manual Download Page 25](http://html1.mh-extra.com/html/fuji-electric/zss-7/zss-7_instruction-manual_2341920025.webp)
- 18 -
INZ-TN7ZSS-E
(14) Adjust the light quantity so that the light quantity value becomes the neighborhood of
the voltage value of the light quantify which is described in a nameplate. If the angle is
adjusted with the furnace operated, it may not become the neighborhood of the light
quantity value described in a nameplate due to the effect of dust, etc. (For the analyzer
with a dust measuring function, record the voltage value of received light quantity after
installation. (refer to 4.6)
↓
(15) Enter the length of the stack, referring to “6.5 Parameter setting”.
↓
(16) For the analyzer with a dust measuring function, if dust does not exist inside the stack,
perform zero adjustment of dust. If you analyze dust manually, measure the average dust
concentration. (After the manual analysis, perform matching).
↓
(17) Make a setting of item to be output in reference to “6.8 Selecting analog output”.
↓
(18) Make a analog output setting in reference to “6.9 Fine adjustment of analog output val-
↓
(19) Make settings of analog inputs such as, gas temperature and water in reference to “6.7
Analog input”. If there is no analog input, select a fixed value to input a parameter.
Make sure to set “Gas temperature", “O
2
” and “Water”. Otherwise, proper measurement
can not be performed. In addition, a gas temperature when furnace stops working differs
from the fixed “gas temperature”, an error many be caused in measurement.
↓
(20) If necessary, make a setting of parameter.
↓
(21) Establish wiring connection of analog input and analog output.
↓
(22) Establish wiring connection of contact input and contact output.
↓
(23) As needed, adjust analog output in reference to “6.9 Fine adjustment of analog output
↓
(24) As needed, check alarm output in reference to “6.10 Checking alarm output”.