![Fuji Electric ZSS-7 Instruction Manual Download Page 75](http://html1.mh-extra.com/html/fuji-electric/zss-7/zss-7_instruction-manual_2341920075.webp)
- 68 -
INZ-TN7ZSS-E
6.4.2 Remote hold (DI3 terminal)
Output hold can be performed by remote according to the external contact input (DI3 terminal, option).
The value to hold output is “Last Meas.” only.
Apply rectangular waveform (pulse width: 2.0 sec or more) to a remote hold input terminal to hold analog
output. Applying it again cancels the hold.
2.0s or more
2.0s
2.0s
2.0s or more
Remote hold signal
Output hold
During hold
Open
Short-circuit