3-21
Displaying running status
To display the running status in hexadecimal format, each state has been assigned to bits 0 to 15 as
listed in Table 3.12. Table 3.13 shows the relationship between each of the status assignments and
the LED monitor display. Table 3.14 gives the conversion table from 4-bit binary to hexadecimal.
Table 3.12 Running Status Bit Allocation
Bit Notation
Content
Bit
Notation
Content
15 BUSY
1 when function code data is being
written.
7
VL
1 under voltage limiting control.
14
Always 0.
6
TL
Always 0.
13
WR
Always 0.
5
NUV
1 when the DC link bus voltage is
higher than the undervoltage level.
12 RL
1 when communication is enabled
(when ready for run and frequency
commands via communications
link).
4 BRK
Always
0.
11
ALM
1 when an alarm has occurred.
3
INT
1 when the inverter output is
stopped.
10
DEC
1 during deceleration.
2
EXT
1 during DC braking.
9 ACC
1
during
acceleration.
1 REV
1 during running in the reverse
direction.
8
IL
1 under current limiting control.
0
FWD
1 during running in the forward
direction.
Table 3.13 Running Status Display
LED No.
LED4
LED3
LED2
LED1
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Notation
BUSY
WR RL
ALM DEC ACC
IL
VL
TL
NUV BRK
INT
EXT REV FWD
Binary
1
0
0
0
0
0
1
1
0
0
1
0
0
0
0
1
Example
Hexa-
decimal
on the
LED
monitor
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...