2-13
h
Main circuit power input terminals, L1/R, L2/S, and L3/T (for three-phase voltage input)
or L1/L and L2/N (for single-phase voltage input)
1) For safety, make sure that the molded case circuit breaker
(MCCB) or magnetic contactor (MC) is turned off before
wiring the main circuit power input terminals.
2) Connect the main circuit power supply wires (L1/R, L2/S
and L3/T or L1/L and L2/N) to the input terminals of the
inverter via an MCCB or residual-current-operated pro-
tective device (RCD)/ a ground fault circuit inter-
rupter(GFCI)*, and MC if necessary.
It is not necessary to align phases of the power supply
wires and the input terminals of the inverter with each
other.
* With overcurrent protection
Figure 2.10 Main Circuit Power Input
Terminal Connection
It is recommended that a magnetic contactor be
inserted that can be manually activated. This is to
allow you to disconnect the inverter from the power
supply in an emergency (e.g., when the protective
function is activated) so as to prevent a failure or
accident from causing the secondary problems.
2.3.6 Replacing the main circuit terminal block (TB) cover
1) As shown in Figure 2.11, pull out the wires from the main circuit terminals in parallel.
2) Hold both sides of the main circuit TB cover between thumb and forefinger and slide it back
into place. Pull the wires out through the grooves of the main circuit TB cover.
Replace the main circuit TB cover, taking care not to apply any stress to the wires. Applying
stress to the wires will impose a mechanical force on the screws on the main circuit ter-
minals, which may loosen the screws.
Figure 2.11 Putting Back the Main Circuit Terminal Block (TB) Cover
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...