6-1
Chapter 6 TROUBLESHOOTING
6.1 Before Proceeding with Troubleshooting
If any of the protective functions have been activated, first remove the cause. Then, after
checking that the all run commands are set to off, reset the alarm. Note that if the alarm is reset
while any run commands are set to on, the inverter may supply the power to the motor which may
cause the motor to rotate.
Injury may occur.
-
Even though the inverter has interrupted power to the motor, if the voltage is applied to the
main circuit power input terminals L1/R, L2/S and L3/T (L1/L and L2/N for single-phase
voltage input), voltage may be output to inverter output terminals U, V, and W.
-
Some electric charge may remain in the DC link bus capacitor even after the power is turned
off. Therefore, it may take some time until the DC link bus voltage reaches a safe level.
Before touching the circuit, wait for at least five minutes after the power has been turned off
and check that the DC voltage between main circuit terminals P (+) and N (-) is less than +25
VDC using a multimeter.
Electric shock may occur.
Follow the procedure below to solve problems.
(1) First, check that the inverter is correctly wired, referring to Chapter 2, Section 2.3.5 "Wiring for
Main Circuit Terminals and Grounding Terminals."
(2) Check whether an alarm code is displayed on the LED monitor.
If any problems persist after the above recovery procedure, contact your Fuji Electric representative.
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...