The wiring procedure for the FRN001C1S-2U is given below as an example. For other inverter types,
perform wiring in accordance with their individual terminal arrangement. (Refer to page 2-3.)
c
Grounding terminal (
G)
Be sure to ground either of the two grounding terminals for safety and noise reduction. It is stipulated
by the Electric Facility Technical Standard that all metal frames of electrical equipment must be
grounded to avoid electric shock, fire and other disasters.
Figure 2.4 Grounding Terminal
Wiring
Grounding terminals should be grounded as follows:
1) Connect the grounding terminal of the 230 V or 460 V class
series of inverters to a ground electrode on which class D or C
grounding work has been completed, respectively, in confor-
mity to the Electric Facility Technical Standard.
2) Connect a thick grounding wire with a large surface area and
which meets the grounding resistance requirements listed in
Table 2.6. Keep the wiring length as short as possible.
Above requirements are for Japan. Ground the inverter
according to your national or local Electric code require-
ments.
d
Inverter output terminals, U, V, W and grounding terminal (
G)
1) Connect the three wires of the three-phase motor to terminals
U, V, and W, aligning phases each other.
2) Connect the grounding wire of terminals U, V, and W to the
grounding terminal (
G).
Figure 2.5 Inverter Output Ter-
minal Wiring
-
The wiring length between the inverter and motor
should not exceed 164ft (50m). If the wiring length
exceeds 164ft (50m), it is recommended that an output
circuit filter (option) be inserted.
-
Do not use one multicore cable to connect several
inverters with motors.
Table 2.6 Grounding Stipulated in the Electric Facility Technical Standard
Supply voltage
Grounding work class
Grounding resistance
Three-phase 230 V
Single-phase 230 V
Single-phase 115 V
Class D
100
:
or less
Three-phase 460 V
Class C
10
:
or less
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...