5-20
Use auto-energy saving only where the base frequency is 60 Hz or lower.
If the base frequency is higher than 60 Hz, then you may get little or no
energy saving effect.
The auto energy saving operation is designed for use with the frequency
lower than the base frequency. If the frequency becomes higher than the
base frequency, the auto energy saving operation will be invalid.
For the auto energy saving function, which is related to the motor char-
acteristics, you need to consistently set the voltage at the base frequency
(F05) and motor parameters P02, P03 and P99 appropriately for the motor
rating and characteristics.
Given below are examples of proper setting in combination with F09 and F37.
If you do not select auto energy saving operation
Load type
To select manual torque
boost, set:
To select automatic torque
boost, set:
Variable torque
F37 = 0
F09 = 0.0 to 20.0 (%)
Constant torque
F37 = 1
F09 = 0.0 to 20.0 (%)
F37 = 2
If you select auto energy saving operation
Load type
To select manual torque
boost, set:
To select automatic torque
boost, set:
Variable torque
F37 = 3
F09 = 0.0 to 20.0 (%)
Constant torque
F37 = 4
F09 = 0.0 to 20.0 (%)
F37 = 5
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...