7-7
7.4 Insulation
Test
Because an insulation test is made in the factory before shipment, avoid a Megger test.
If a Megger test is unavoidable, follow the procedure below. Because a wrong test procedure will
cause breakage of the inverter, take sufficient care.
A dielectric strength test will cause breakage of the inverter similarly to the Megger test if the test
procedure is wrong. When the dielectric strength test is necessary, contact your Fuji Electric
representative.
(1)
Megger test of main circuit
1) Use a 500 VDC Megger and shut off the main power supply without fail during measurement.
2) If the test voltage leaks to the control circuit due to the wiring, disconnect all the control wiring.
3) Connect the main circuit terminals with a common cable as shown in Figure 7.2.
4) The Megger test must be limited to across the common line of the main circuit and ground (
).
5) 5
M
:
(1 M
:
for the EMC filter built-in type of inverters) or a larger value displayed at the Megger
indicates a correct state. (The value is for a discrete inverter.)
Figure 7.2 Megger Test
(2) Dielectric strength
test of control circuit
Do not perform a Megger test or dielectric strength test for the control circuit. Prepare a high
resistance range tester for the control circuit.
1) Disconnect all the external wiring from the control circuit terminals.
2) Perform a continuity test to the ground. 1 M
:
or a larger measurement indicates a correct state.
(3) Dielectric strength
test of external main circuit and sequence control circuit
Disconnect all the inverter terminals so that the test voltage is not applied.
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...