Installers and service technicians
Parameter list - Lambdatronic P 3100
Page 70
B0190806
s
7
Heating times...
←
←
←
←
Heating prog.
1...
←
←
←
←
Heating phase
1 start
06:00
Lowered outside of heating phases.
Only in conjunction with
heating circuit control.
Heating phase
1 end
11:00
Heating phase
2 start
15:00
Heating phase
2 end
23:00
Heating prog. 2...
Heating prog. 3...
Heating prog. 4...
Heating prog. 5...
Heating prog. 6...
Heating prog. 7...
Heating prog. 8...
Heating prog. 9...
Heating prog. 10...
Heating prog. 11...
Heating prog. 12...
Heating prog. 13...
Heating prog. 14...
2 heating phases each,
like heating prog. 1.
You can program up to 14 heating times
each with two heating phases.
These are assigned to the individual days
of the week in the parameter “Heating
circuit 1-4 / weekly program”.
Heating
circuit 1
...
←
←
←
←
Weekly
program
MoTuWeThFrSaSu
1 1 3 1 1 2 5
Heating time programs 1-14 are assigned
to the days of the week for heating circuit
1.
Heating curve
...
←
←
←
←
Flow temp. At
external –10°C 60°
←
←
←
←
Only in conjunction
with heating circuit
control.
Flow temp. at outer
+10°C
40°
←
←
←
←
You can adjust the heating curve to the
relevant system in these two work points.
Room temp.
set value
20°
←
←
←
←
Target room temperature value during the heating
phase
only with remote control
Room temp.SV reduced
amount
16°
←
←
←
←
Target room temperature value during the drawdown
phase
only with remote control
Room temp. contr.
factor (Kp).
6.0
←
←
←
←
Influencing factor of room temp. on flow temp. If the
room temp. deviates by 1°C or more, the target value
for the flow temperature resulting from the set heating
curve is corrected by this value.
±
(only with remote
control)
Flow temperature
reduction of
15°
←
←
←
←
The flow temperature is reduced by this value in
drawdown phase.
Ext. temp. heating
limit
18°
←
←
←
←
If the external temperature exceeds this heating limit
during the heating phase, the heating circuit pump and
mixer are switched off.
Ex.temp.heatlim.
reduced amount
7°
←
←
←
←
If the outside temperature exceeds this heating limit
during the drawdown phase, the heating circuit pump
and mixer are switched off.
Flow temp. max.
value
75°
←
←
←
←
Maximum temperature for limiting flow temperature.
(system dependent: floor heating, radiators,..)
Mixer Ty
240s
←
←
←
←
Set mixer runtime of heating circuit mixer in use!
Note: do not set mixer time under 150s!