Installers and service technicians
Initial startup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria
Page 65
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com
B0190806
7
NOTE for Uno/Eco/Komfort universal suction systems and bag silo
systems:
To fill the suction unit container set the “Fill” parameter in the “Manual
operation” menu to “ON”. The suction system starts and the suction unit
container is filled with fuel until the switch point of the level sensor is
reached.
NOTE for screw suction systems, underground tank (external
discharge):
To fill the suction unit container, set the “Start of automatic filling” in
the “Outfeed” menu to one minute after the current time. This starts the
suction system a minute later and the suction unit container is filled with
fuel until the switch point of the level sensor is reached. After filling,
reset the parameters to the desired time.
7.4.6
Setting parameters
After starting the boiler with the
key, “Winter operation” mode is set
according to factory settings.
For other modes see
4.2.1
Modes
You need to check and if necessary adjust the following parameter:
Heating curve
Radiator or floor heating
Minimum flue gas
temperature
The value should be adjusted for chimneys without
tiles or a stainless steel pipe.
Mode
See
4.2.1
Modes
Induced draught offset
Settings are made by the service technician using
an analytical device
The other parameters are factory set in such a way that in most cases
optimal operation is possible without making further changes to the
parameters.
The following parameters, however, can/should be adjusted as desired
by the customer:
- Target boiler temperature
- Storage times
- DHW tank times
- Solar parameters
- Reduction programs
- Heating circuits 1 - 4
- Start of automatic filling (for suction systems)
- Boiler times (only for transitional operation)