Troubleshooting
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria
Page 47
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com
B0190806
6
Error text
Code Type
Cause of error
Error correction
Boiler remains in “IGNITE”
state longer than the
“Ignition time max”:
Acknowledge error
NOTE: After acknowledging the error, error correction starts
immediately. Keep the doors of the boiler closed!
After error correction starts, check if the induced draught fan is
running
CAUTION! In case of defective induced draught fan inform the
heating engineers or Fröling customer services!
When error correction has been automatically carried out (approx.
20 min) the warning, “Clean/ check burner”, is shown on the
display.
After you have done this, open the insulating door and
combustion chamber door
Clean embers, fuel and slag from the pellet burner (see
chapter on maintenance)
Clean the flue gas guide in the boiler up to the mouth of the
chimney
Empty the ash drawer if necessary
Acknowledge warning
Ignition failed
013
F
•
Too few pellets in
combustion bowl
•
Defective ignition
•
Stoker not feeding
Refill pellets in storage tank,
check discharge and stoker
ATTENTION! Do not feed any
pellets into the pellet burner
manually - danger of flash fires!
Have the ignition checked by
professionals
Check stoker drive