Installers and service technicians
Initial startup
Page 64
B0190806
s
7
Setting sensor “Level Max”
In delivery configuration, the factory settings of
the sensor are secured with a seal.
Changes to the settings should only be carried out
by qualified technicians.
The monitoring LED (1) should only illuminate
when identifying materials!
If the monitoring LED is constantly lit, the
sensitivity is set too high!
Reduce the sensitivity by turning the
adjusting screw (2) to the left
If the monitoring LED does not react when
pellets are being fed in, the sensitivity is set
too low!
Increase the sensitivity of the adjusting
screw by turning to the right
7.4.5
Feeding fuel into the combustion chamber
Before the initial setup there are no pellets in the stoker and discharge
screw. With the “Manual fuel” parameter, pellets are fed into the
combustion chamber.
MANUAL FUEL
ON
←
←
←
←
If the first pellets are visible in the combustion bowl,
set the “Manual fuel” parameter back to “OFF”.
CAUTION: Placing too many pellets in the combustion bowl
can increase the danger of flash fires!
Combustion bowl correctly
filled
Too many pellets in the
combustion bowl
1
2