Lambdatronic P 3100 control system
Display messages
Page 26
B0190806
s
4
4.2.2
Operating statuses
Preparation
The induced draught fan is switched on.
Heating up
The combustion bowl is filled with pellets. The supply air fan, the induced
draught fan and the igniter are turned on.
Pre-heating
The pellets are pre-warmed with the fan-assisted ignition and a bed of embers
is formed. No fuel slide-in unit.
Ignition
The pellets are ignited with the fan-assisted ignition. The flame is spread across
the whole combustion bowl. The supply air fan, the ID fan, and the slide-in unit
can be set in the “Ignition” menu.
Heating
The Lambdatronic controls combustion according to the target boiler values.
Constant burn
The boiler has reached the specified temperature and there is no reduction in
temperature. The supply air fan, the ID fan, and the slide-in unit are
deactivated.
STBY. Wait 1
The supply air fan and perhaps the ID fan are running too slowly (“Fan during
shut down”) to burn the remaining pellets. No slide-in.
STBY. Feed 1
Safety slide-in after the first wait time. As with status “STBY. Wait 1”, but
with slide-in, in accordance with the parameter, “Feed off”.
STBY. Wait 2
The supply air blower fan and the induced draught are switched off, no slide-in.
STBY. Feed 2
Safety slide-in after the second wait time. As with status “STBY. Wait 2”, but
with slide-in, in accordance with the parameter, “Feed off”.
Fault
ATTENTION - Fault!
Error correction 20 min
When the faults “Ignition failed”, “Safety time elapsed too low”, “Safety time
O2 too high” and “Pressure monitor comb chamb” are acknowledged, error
correction starts. When error correction has been carried out (approx. 20 min)
the warning, “Clean/ check burner”, is shown on the display. The warning can
only be acknowledged with the enter key after checking the burner.
Burner Off
This status is reached by pressing the
key when store or DHW tank loading
has finished, or after acknowledging an error message, which requires a
shutdown. All parts of the boiler stop. The system now only regulates the
connected heating components.