5.3 Filling the store with fuel
Note the following when loading the machine with fuel:
❒ Only use permitted fuels!
⇨ See "Permitted fuels" [page 8]
❒ Remove foreign bodies from the store before filling
NOTICE! Systems in which the fuel is delivered by tanker and is blown into the store
space must be fitted with a rotary valve.
For blowing in fuel the following precautions also apply:
CAUTION
Blowing in fuel when the boiler is switched on:
The underpressure generated from blowing in fuel can lead to smoke being
sucked back into the store if the boiler is switched on. Possible excess pressure
could cause smoke to escape into the installation room, possibly resulting in injury
and damage!
Therefore, before blowing in the fuel:
❒ Switch off the power supply to the entire system
➥ Depending on the model via boiler, expansion switch cabinet, etc.
❒ Allow the system to cool for at least two hours
5.3.1 Loading of fuel for a partially emptied store with rotary agitator
If there is still sufficient fuel in the store (the head of the rotary agitator is completely
covered with fuel and the rotary agitator arms are not extended), the store can be
filled:
❒ Load the fuel at the filling opening
Operating the system
5
Filling the store with fuel
Installation Instructions TGR 110/150/200 | M1390116_en
33