background image

RWB II ROTARY SCREW COMPRESSOR UNITS

OPERATION

S70-200 IOM
Page 20

COMPRESSOR OIL COOLING SYSTEMS

The RWB II unit can be equipped with one of several sys tems 
for controlling the compressor oil tempera ture. They are single 
or dual-port liquid injection, or thermo syphon and water-
cooled oil coolers. Each system is autom ati cally con trolled, 
independent  of compressor loading or unloading. 

Oil cooling systems should maintain oil temperature within 
the following ranges for R-717 and R-22:

 Liquid 

Injection 

External*

 

Oil Cooling 

Oil Cooling

 

130 - 170°F 

120 - 160°F

* Thermosyphon oil cooling (TSOC) or Water-cooled oil 
cool ing (WCOC).

SINGLE-PORT LIQUID INJECTION

The single-port liquid injection system is desig ned to per mit 
liquid refrigerant injection into one port on the com pres sor 
at any given moment and operates as outlined.

Solenoid valve SV5 is energized by the micro processor 
when the temperature sensor, in stalled in the oil manifold, 
ex ceeds the LICO set point.  High pressure liquid refriger ant 
is then supplied to the tempera ture control valve (TCV). The 
tem per a ture control valve is equal ized to a constant back 
pres sure by the dif feren tial pressure control valve (PDCV). 
The differential pressure control valve uses dis charge gas 
to maintain downstream pressure. The gas downstream of 
the differential pressure control valve is bled off to the com-
 pres sor suction to ensure steady and constant opera tion of 
the valve.  

RWB II BOOSTER OR SWING DUTY

APPLICATION

Discharge gas from the high stage compressor is required 
to assist the differen tial pressure control valve (PDCV) in 
pro vid ing the temperature control valve (TCV) with a con stant 
back pressure.

A solenoid valve SV6 is installed before the differential 
pres sure control valve (PDCV) to prevent migration of high 
pres sure gas during shutdown. A Frick-installed timer limits 
the high pressure gas to only thirty seconds duration, since 
in ter me di ate gas pressure and spring tension are suffi cient to 
maintain closure on unit shutdown. A metering valve is also 
provided for use as a service valve and to allow discharge 
gas fl ow regulation to prevent excessive force and resulting 
closure “hammering”. 

A fi eld-installed 1/4 inch OD tubing connection is required 
between the high stage compressor discharge piping line (or 
receiver) and the check valve.

DUAL-PORT LIQUID INJECTION

The dual-port liquid injection system is design ed to obtain 
the most effi cient compressor performance at high and low 
compression ratios by permitting injection of liquid refriger ant 
into one of two ports optimally located on the com pressor. 
This minimizes the performance penalty incurred with liquid 
injection oil cooling.

The dual-port system contains all the com ponents of the 
sin gle-port system with the addition of a double acting so-
 le noid valve SV7 and operates as outlined.

Solenoid valve SV5 is energized by the micro processor when 
the temperature sensor, in stalled in the oil manifold, ex ceeds 
the LICO set point. Liquid refrigerant is then passed through 
the tempera ture control valve (TCV) to the doub le-acting so-
lenoid valve SV7. Depending on the compressor’s op er at ing 
volume ratio (Vi), the micropro cessor will select the fl ow of 
the liquid refrigerant to either com pressor port SL-1 or SL-2, 
whichever is more effi cient.

When the compressor operates BELOW 3.5 Vi, compres sor 
port SL-1 supplies the liquid cool ing.  When the (Vi) ris es 
ABOVE 3.5 Vi, port SL-2 supplies the liquid cooling.

The temperature control valve is equalized to a constant back 
pressure by the differential pres sure control valve (PDCV).

Both the differential pressure control valve (PDCV) and 
the double-acting solenoid valve SV7 use discharge gas to 
main tain downstream pressure. The gas downstream of both 
valves is bled off to the compres sor suction to ensure steady 
and constant operation of the valves.

LIQUID INJECTION ADJUSTMENT

PROCEDURE

Adjustments must be made to ensure the oil is at the proper 
temperature. When the adjustments have been made cor-
rectly, the oil temperature, the discharge temperature and 
the temperature of the oil in the separator should all be ap-
proximately the same. (Refer to P&I Diagram)

 Carefully insert The bulb from the thermal expansion valve 
( TXV ) into the well in the discharge pipe between the com-
pressor and the oil separator. Then open the valve to the oil 
separator high pressure connection. 

Next, open the refrigerant supply valve, remove the cap on 
the pressure regulating valve (PCV ), and close the adjust-
ing valve.

For low temperature oil – 125° to 135°F

After the unit has been started, wait for the oil temperature to 
reach 122°F. This is the preprogrammed temperature to open 
the liquid feed solenoid in the liquid injection supply line.

Open the adjusting valve only until the needle on the gauge 
begins to move a very small amount. 

Next, adjust the pressure regulating valve to approximately 
80 psig by turning the adjustment ring inside the top of the 
valve with  a 5/16" Allen wrench. Turn the wrench clockwise 
to raise the oil temperature, and counterclockwise to lower 
the oil temperature.

After the adjustment s been, made wait until the oil and 
discharge temperatures have had a chance to stabilize 
before readjusting. The end result should be between 135° 
and 140°F.

For high temperature oil – 160° to 170°F

After the unit has been started, wait for the oil temperature to 
reach 122°F. This is the preprogrammed temperature to open 
the liquid feed solenoid in the liquid injection supply line.

Open the adjusting valve only until the needle on the gauge 
begins to move a very small amount.

Summary of Contents for RWB II

Page 1: ...MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READTHOROUGHLY BEFORE BE GINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUC TIONS COULD RESULT IN DAMAGE OR IMPROPER OPERATION...

Page 2: ...t in death or serious injury Indicates a potentially hazardous situation or practice which if not avoided will result in death or serious injury SAFETY PRECAUTION DEFINITIONS Indicates a potentially h...

Page 3: ...lator or slugging protection that load surges are known and provisions made for control operating cycles and defrosting periods are reasonable and that high side condensers are sized within system and...

Page 4: ...essor package When installing on the upper floors of buildings extra precau tions should be taken to prevent normal package vibration from being transferred to the building structure It may be necessa...

Page 5: ...make sure that they are free of burrs dirt and grit CH COUPLING DATA TABLE 3 Check that the keys fit the hubs and shafts properly CH COUPLING The T B Woods Elastomeric CH Coupling is used in most app...

Page 6: ...ocated Injury may occur if loose clothing etc becomes entangled on the spinning motor shaft If the motor is coupled to the compressor using a fixed end play coupling such as the Series 52 coupling and...

Page 7: ...lignment compensates for thermal growth when the unit is at operating temperature The following procedure is applicable to both the CH and DBZ B couplings Dial indicators are to be used to measu re th...

Page 8: ...isalignment is within specified tolerance 10 Check parallel lateral misalignment by positioning dial indicator so the stem is in contact with the rim of the com pressor hub at 3 o clock as shown in Fi...

Page 9: ...charge checked periodically COMPRESSOR UNIT OIL DO NOT MIX OILS of different brands manufacturers or types Mixing of oils may cause excessive oil foaming nuisance oil level cutouts oil pressure loss g...

Page 10: ...and vaporize The vapor rises in the return line The density of the refrigerant liquid vapor mixture in the return line is considerably less than the density of the liquid in the supply line This imbal...

Page 11: ...pply of high pres sure liquid refrigerant be provided to the injection system at all times Two items of EXTREME IMPORTANCE are the design of the receiver liquid injection supply and the size of the li...

Page 12: ...liquid injection oil cooling are given in the following table LIQUID LINE SIZE and RECEIVER VOLUME LINE SIZE POUND LIQUID RWB II SCH 80 OD PER VOLUME MODEL PIPE TUBING 5 MIN CU FT R 717 HIGH STAGE 100...

Page 13: ...ect Expansion Economizer System Figure 11 Shell and Coil Economizer System Figure 14 Multiple Compressor Economizer System Figure 13 Flash Economizer System For refrigeration plants employing multiple...

Page 14: ...the use of UPS power systems in front of the Quantum panel With a UPS power system providing shutdown protection for the Quantum the panel may not see the loss of the 3 phase voltage on the motor bec...

Page 15: ...each normally open compressor motor and oil pump motor starter auxiliary contact should be supplied In addition to the compressor and oil pump motor starter coils the CT and CPT secondaries should be...

Page 16: ...VE FERRITE TUBE WHEN SOLA IS ADDED 6B 6 H NOTE AT SOLA ASSEMBLY MAKE WIRES 6 2 GND 6B 2B 10 FT LONG CUT WIRESTO LENGTH AT INSTALLATION H5 REGULATOR H3 H4 OUTPUT INPUT X1 120 240 V IN 120 V OUT SOLA 63...

Page 17: ...seal well below discharge pressure for increased seal life 10 Oil injected into the rotors to maintain good volumetric and adiabatic efficiency even at very high compression ratios 11 Shaft rotation c...

Page 18: ...START VALVE DEMAND PUMP OIL SYSTEM This system is designed to provide adequate compressor lubrication for some high stage applications that operate with low differential pressure across the compresso...

Page 19: ...rough valve ports P and A to cylinder port SC 1 and enters the unload side of the cylinder Simultaneously oil contained in the load side of the cylinder flows out com pressor port SC 2 through valve p...

Page 20: ...system contains all the components of the single port system with the addition of a double acting so lenoid valve SV7 and operates as outlined Solenoid valve SV5 is energized by the microprocessor whe...

Page 21: ...injection valve look at the power head of the Thermal Expansion Valve If the unit is using Ammonia as a refrigerant and is for low temperature the Sporlan number on the power head should be Y764 or Y8...

Page 22: ...diagram in S90 010 M Quantum or S70 200 OM Plus shows the wiring included when required Introduction of high discharge pressure gas is made to the check valve A timer limits the high pressure gas to o...

Page 23: ...ressor s economizer port If an electric shut off is not installed in the economizer vapor line valve HV 2 must remain closed to avoid a gas bypass from the economizer line through the suction check va...

Page 24: ...hut down on Comp Differential 4 After running the unit for approximately three hours adjust liquid injection oil cooling if applicable If unit has thermosy phon or water cooled oil cooling adjust wate...

Page 25: ...pplicable Re move tags 3 Close disconnect switches for compressor motor and oil pump starters 4 Turn off oil heater circuit breaker 5 Perform checkpoints on prestart check list then start unit GENERAL...

Page 26: ...vice valves of the standby filter Open inlet service valve slowly to prevent a sudden pressure drop which could cause an oil filter dif ferential alarm 2 Close outlet then inlet service valves of fil...

Page 27: ...alescer filter retainer 4 Remove retainer coalescer filter element and 2 O rings Discard filter elements 5 Install new coalescer filter element s Seat element in center of locating tabs on separator b...

Page 28: ...GRAPHITE BUSHINGS fFigure 26 Thrust Bearing assembly GG HJ HL Figure 27 Thrust Bearing assembly AS AK AL 5 Insert a brass bar or piece of hardwood in the port open ing and between rotor teeth to keep...

Page 29: ...sure both are free from dirt and grit Coat outer diameter of seal seat and inner diameter of seal housing bore with refrigeration oil 3 Start seal seat in seal housing bore If force is nec essary pro...

Page 30: ...ditional end clear ance 0 004 for GG HJ and HL size pumps and 0 005 for AS AK and AL size pumps Pump Distance in on O D End Clearance Size of Bearing Housing in GG 7 16 003 HJ HL 9 16 003 AS AK AL 1 2...

Page 31: ...a Starving or cavitating increase suction pipe size or reduce length b Strainer partially clogged clean c Air leak in suction piping or along pump shaft d Running too slowly is motor the correct spee...

Page 32: ...rom the new unit at start up as the base line reference 3 Evaluate vibration readings carefully as the instrument range and function used can vary Findings can be easily misinterpreted 4 Vibration rea...

Page 33: ...and servicing Continual recording of gauge pressures temperatures and other pertinent information enables the observer and serviceman to be constantly familiar with the operation of the system and to...

Page 34: ...perheat 4 Excessively high discharge pressure 5 Inadequate refrigerant charge or low receiver level 6 Excessively high or low temperature coolant to the oil cooler 7 Liquid return from system slugging...

Page 35: ...cer leads by loosening the terminal screws for the transducer to be changed 6 Tape a 3 ft length of pull wire to the leads of the transdu cer to be removed Below 0 PSIG measured in inches of mercury P...

Page 36: ...TE The total travel on theVOLUMIZER potentiometer is 394 inch SV POSITION POTENTIOMETER REPLACEMENT AND ADJUSTMENT The Slide Valve Position potentiometer is located on the end of the compressor unload...

Page 37: ...crews 7 Apply DIN connector plug to transmitter 8 Turn on control power Figure 34 TROUBLESHOOTING THE RWB II COMPRESSOR SYMPTOM PROBABLE CAUSES and CORRECTIONS EXCESSIVE NOISE and VIBRATION Main oil i...

Page 38: ...operating both ways clean Solenoid may be mechanically actuated by inserting a piece of 3 16 rod against armature pin and pushing spool to opposite end If valve works problem is electrical SLIDE STOP...

Page 39: ...ervice valves are open Filter cartridges may be blocked Check PSID across filters Strainer may be blocked Clean Oil pressure regulator set too low or stuck open Readjust or repair Pump worn out Repair...

Page 40: ...hieved by increasing or decreasing discharge tube size NOTE DO NOT ATTEMPT TO ADJUST SUPERHEAT ADJUSTMENT STEM ON BOTTOM OF VALVE IN AN EF FORT TO CHANGE THE VALVE S PERFORMANCE THIS ADJUSTMENT IS PRE...

Page 41: ...t seems to be a total absence of oil cooling you will need to check the action of the valve To check the action you will need to remove the cap flange and disc guide If the hole in the valve plate is...

Page 42: ...e closed the oil pressure should be 1 1 times suction pressure 15 psi Differential pressure is defined as de fined as discharge pressure minus suction pressure The shutdown should occur if the conditi...

Page 43: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 43 P I DIAGRAM...

Page 44: ...PRESSURE SAFETY VALVE SP SUCTION PRESSURE STR STRAINER TAH HIGH TEMPERATURE ALARM TAHH HIGH TEMPERATURE SHUTDOWN TAL LOW OIL TEMPERATURE ALARM TALL LOW OIL TEMPERATURE SHUTDOWN TC TEMPERATURE CONTROLL...

Page 45: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 45 P I DIAGRAM LIQUID INJECTION SINGLE PORT P I DIAGRAM LIQUID INJECTION DUAL PORT...

Page 46: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 46 P I DIAGRAM LIQUID INJECTION BOOSTER...

Page 47: ...erride any rules by the NEC but are to be used in conjunction with the NEC code WIRE SIZING Size supply wires one size larger than required for amperage draw to reduce instantaneous voltage dips cause...

Page 48: ...the same conduit with 120 volt wires Figure 46 Never run any wires through an electronic control panel that do not relate to the function of the panel Electronic control panels should never be used as...

Page 49: ...y destroy the electronics If the electronic control panel has a starter built into the same panel be sure to run the higher voltage wires where indicated by the manufacturer EMI from the wires can int...

Page 50: ...RWB II PLUS ROTARY SCREW COMPRESSOR UNITS FORMS S70 200 IOM Page 50 OPERATING LOG SHEET...

Page 51: ...ontrol wiring is run in a separate conduit from oil pump and compressor motor wiring __ Confirm no high voltage wiring enters the micro panel at any point __ Check current transformer for correct sizi...

Page 52: ...and Date _________ Analog Board 1 Serial ______________Rev _____ U13 Analog Ver _________ and Date ______________ Analog Board 2 Serial ______________Rev _____ U13 Analog Ver _________ and Date _____...

Page 53: ...nment Ambient Temperature at Time of Alignment _______ Oil Separator Temperature at Time of Alignment ________ Motor Coupling Type ___________ Size ___________ Distance Between Coupling Hub Faces ____...

Page 54: ...___________________ Installing Contractor _____________________________ Address ______________________________________ Service Technician ______________________________ Equipment ID As in Microlog ___...

Page 55: ...0 200 PSIA Quantum only 1 ALL 913A0110H01 Transducer Pressure 0 500 PSIA Quantum only 1 ALL 913A0110H02 Potentiometer Slide Stop 1 ALL 111Q0041148 Kit Potentiometer Slide Valve 1 ALL 534D0523G02 Valve...

Page 56: ...systems Q NET means precise control 24 hours a day seven days a week Q NET distributed architecture means faster easier economical installations Q NET delivers increased operating efficiency and lowe...

Reviews: