Issue/Rev. 0.2 (12/12)
MN0M023 • Page 41
Device Functions Proline Promass 83
5 Block USER INTERFACE
ASSIGN
(continued)
Advanced options with optional software package CONCENTRATION:
TARGET MASS FLOW
% TARGET MASS FLOW
TARGET VOLUME FLOW
% TARGET VOLUME FLOW
CORRECTED TARGET VOLUME FLOW
CARRIER MASS FLOW
% CARRIER MASS FLOW
CARRIER VOLUME FLOW
% CARRIER VOLUME FLOW
CORRECTED CARRIER VOLUME FLOW
% BLACK LIQUOR
°BAUME
°API
°PLATO
°BALLING
°BRIX
OTHERS (_ _ _ _ flexible concentration)
Advanced options with optional software package ADVANCED DIAGNOSIS:
MASS FLOW DEVIATION
DENSITY DEVIATION
REFERENCE DENSITY DEVIATION
TEMPERATURE DEVIATION
TUBE DAMPING DEVIATION
ELECTRODYNAMIC SENSOR DEVIATION
OPERATING FREQUENCY FLUCTUATION DEVIATION
TUBE DAMPING FLUCTUATION DEVIATION
100% VALUE
(2201)
!
Note!
This function is not available unless one of the following was selected in the ASSIGN
function (2200):
• MASS FLOW IN %
• VOLUME FLOW IN %
• CORRECTED VOLUME FLOW IN %
Use this function to define the flow value to be shown on the display as the 100% value.
User input:
5-digit floating-point number
Factory setting:
10 kg/s, 10 l/s or 10 Nl/s
FORMAT
(2202)
Use this function to define the maximum number of places after the decimal point
displayed for the reading in the main line.
Options:
XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting:
X.XXXX
!
Note!
• Note that this setting only affects the reading as it appears on the display, it has no
influence on the accuracy of the system's calculations.
• The places after the decimal point as computed by the measuring device cannot always
be displayed, depending on this setting and the engineering unit. In such instances an
arrow appears on the display between the measuring value and the engineering unit
(e.g. 1.2
o
kg/h), indicating that the measuring system is computing with more
decimal places than can be shown on the display.
Function description
USER INTERFACE
o
MAIN LINE
o
CONFIGURATION