7 Block OUTPUTS
Device Functions Proline Promass 83
7.1.2
Function group OPERATION
OUTPUTS
E
CURRENT OUTPUT 1
EAA
CONFIGURATION
400
OPERATION
404
CURRENT OUTPUT 2
EAB
CONFIGURATION
400
OPERATION
404
CURRENT OUTPUT 3
EAC
CONFIGURATION
400
OPERATION
404
Function description
OUTPUTS
o
CURRENT OUTPUT (1...3)
o
OPERATION
ACTUAL CURRENT
(4040)
Use this function to view the computed actual value of the output current.
Display:
0.00...25.00 mA
SIMULATION CURRENT
(4041)
Use this function to activate simulation of the current output.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
• The “SIMULATION CURRENT OUTPUT” message indicates that simulation is active.
• The measuring device continues to measure while simulation is in progress, i.e. the
current measuring values are output correctly via the other outputs.
"
Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
CURRENT
(4042)
!
Note!
The function is not visible unless the function SIMULATION CURRENT (4041) is active
(= ON).
Use this function to define a freely selectable value (e.g. 12 mA) to be output at the
current output. This value is used to test downstream devices and the measuring device
itself.
User input:
0.00...25.00 mA
Factory setting:
0.00 mA
"
Caution!
The setting is not saved if the power supply fails.