![FMC Technologies Proline Promass 83 E Description Of Device Functions Download Page 181](http://html.mh-extra.com/html/fmc-technologies/proline-promass-83-e/proline-promass-83-e_description-of-device-functions_2312629181.webp)
Issue/Rev. 0.2 (12/12)
MN0M023 • Page 181
Device Functions Proline Promass 83
11 Block SUPERVISION
ERROR CATEGORY
(8003)
!
Note!
This function is only available if a process error has been selected in the function ASSIGN
PROCESS ERROR (8002).
Use this function to define whether a process error triggers a notice message or a fault
message. If you select FAULT MESSAGES, all outputs respond to an error in accordance
with their defined error response patterns.
Options:
NOTICE MESSAGES (display only)
FAULT MESSAGES (outputs and display)
!
Note!
Press the key
F
twice to call up the function ASSIGN PROCESS ERROR (8002).
ACKNOWLEDGE
FAULTS
(8004)
Use this function to define the measuring device's response to fault messages.
Options:
OFF
The measuring device resumes normal operation when the fault is rectified. The fault
message automatically disappears from the local display.
ON
The measuring device resumes normal operation when the fault is rectified. The fault
message appears in the local display until it is acknowledged by pressing the
F
button.
Factory setting:
OFF
ALARM DELAY
(8005)
Use this function to define a time span for which the criteria for an error have to be
satisfied without interruption before a fault or notice message is generated.
Depending on the setting and the type of error, this suppression acts on:
• Display
• Current output
• Frequency output
• Relay output
• Current input
User input:
0...100 s (in steps of one second)
Factory setting:
0 s
"
Caution!
If this function is activated, fault and notice messages are delayed by the time
corresponding to the setting before being transmitted to the higher-order controller
(process controller, etc.). It is therefore imperative to check in advance in order to make
sure whether a delay of this nature could affect the safety requirements of the process. If
fault and notice messages may not be suppressed, a value of 0 seconds must be entered
here.
Function description
SUPERVISION
o
SYSTEM
o
CONFIGURATION