Power Sum ACR
Power Sum ACR
is calculated from the Attenuation of the disturbing
pair subtracted from the Power Sum NEXT for the pair. The worst case
Power Sum ACR is reported for each pair.
The
POWER SUM ACR
screen displays the pairs in
the column on the left side, followed by the
PSACR in decibels (dB), the margin/limit, and the
frequency. The result for each pair is tagged with a
PASS
or FAIL
indicator.
Press
or
to toggle between Power
Sum ACR results for OMNIS
CANNER
and OMNIR
EMOTE
.
Press
(Graph) to view the graph for the
currently highlighted pair. Attenuation and
PSNEXT are displayed for the frequency indicated
by the cursor position.
Press
(Pairs) to view Attenuation and PS
NEXT graphs for other pairs.
Press ESC to exit the
POWER SUM ACR
screen.