Comark RF500A/AP Service Manual
Tier 3: RF500A Component Level Repair
Tier 3: RF500A Component Level Repair
Operator Technical Competency
The Tier 3 section requires an engineer level operator.
Functional Test Equipment Required
•
RF500A AC Adaptor
•
PoE Injector Mode-A
•
PoE Injector Mode-B
•
DMM
•
Computer running Microsoft Windows with Comark RF500ACONFIG Utility, Comark USB Drivers Version
3.00 or higher, Silicon Labs USB Drivers and Silicon Labs USB manufacturing configuration software must
also be installed.
•
Ethernet cable
Initial Observation
The RF500A Gateway may be initially observed in various states. It is important to record the details about this state
before performing further tests, this information may prove useful in later fault diagnosis.
Referring to both Appendix-A – Front Panel Indicators ,Appendix B – Status Indicators and Appendix C – Website
Error Messages, record carefully which indicators are showing. Of course if a recognised fault is indicated, we could
continue testing to determine whether that particular fault recurs. If the device manages to boot up, Appendix C –
Website Error Messages lists the possible error messages for further fault diagnosis.
Status Indicators
Note that the status indicators as described in Appendix B – Status Indicators are only capable of displaying one fault at
a time. In the event that there my be multiple faults the highest priority fault will be displayed until fixed.
The status indicators are only active for fault status display while the PC module is off, once booted the module has
control of these indicators for activity indication.
Circuit Diagrams
Circuit diagrams and component layouts are available from the Comark Production support site.
•
Circuit Diagram:
A1/CCT/11410
•
Component Layout:
A2/PCL/11412
17 November 2011
Page 37 of 65