Generator Failure
Page 80 AGT 6000 PVMV-N 12V_24V - Chapter D: Generator Failure
D.1.4 Adjustment of the normal rev limitation
Adjusting the lower limitation:
1. Disconnect the plug at the electrical supply line of the actuator.
2. Unclamp the countering nuts with two wrench SW 10.
3. Connect an electrical voltage instrument (voltmeter) with a display range until 100V DC to the
clamps 7 and 8 of the VCS.
4. Be sure that no electrical load is adjusted.
5. Start the generator.
6. Decrease the rev of the generator by turning the spindle of the actuator manually until the volt-
meter reach a value of 23V DC.
7. Both nuts must be screwed tight.
8. Check again if the lower voltage of the generator is limited to min. 23V without load.
Adjusting the upper limitation:
1. Proceed like before and tighten the countering nuts at a voltage of max. 33V without load.
2. Check again if the upper voltage of the generator is limited to this value.
01. Adjusting nut for upper rev limitation
02. Adjusting nut for bottom rev limitation
Fig. D.1.4-1: Normal rev setup
If the adjustment is finished the plug of the actuator must be re-connect for operation.
01
02
Summary of Contents for AGT 6000 PVMV-N
Page 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Page 6: ......
Page 10: ...8 Socket wrench set Hexagon wrench keys ...
Page 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Page 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Page 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Page 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...